ICF-IID Attic Fire Safety Requirement Presenter’s Name: Donald

14 Slides370.04 KB

ICF-IID Attic Fire Safety Requirement Presenter’s Name: Donald Howard Presenter’s Title: Health Insurance Specialist CMS Division: Division of Continuing Care Providers 1

Disclaimers This presentation was prepared as a tool to assist providers and is not intended to grant rights or impose obligations. Although every reasonable effort has been made to assure the accuracy of the information within these slides, the ultimate responsibility for the correct submission of claims and response to any remittance advice lies with the provider of services. This publication is a general summary that explains certain aspects of the Medicare Program, but is not a legal document. The official Medicare Program provisions are contained in the relevant laws, regulations, and rulings. Medicare policy changes frequently, and links to the source documents have been provided within the slides for your reference The Centers for Medicare & Medicaid Services (CMS) employees, agents, and staff make no representation, warranty, or guarantee that this compilation of Medicare information is error-free and will bear no responsibility or liability for the results or consequences of the use of this guide.

Learning Objectives At the conclusion of this presentation, the participant will be able to understand : 1. Regulatory requirements 2. Attic protection requirements for occupied or used attic spaces 3. Attic protection requirements for unoccupied or unused attic spaces 4. Life Safety Code waiver 3

Life Safety Code Final Rule Final rule (CMS-3277-F) was published May 4, 2016 & effective July 5, 2016. https://www.gpo.gov/fdsys/pkg/FR-2016-05-04/pdf/2 016-10043.pdf The final rule updated fire safety requirements for certain providers including intermediate care facilities for individuals with intellectual disabilities (ICF-IID). The final rule adopted the 2012 editions of the National Fire Protection Association's (NFPA) Life Safety Code (LSC) and Health Care Facilities Code. 4

Life Safety Code Attic Fire Safety Requirement LSC was adopted by CMS regulation effective July 5, 2016. Regulation gave ICF-IID until July 5, 2019 to comply with attic fire protection requirements. Beginning July 5, 2019, an ICF-IID must be in compliance with Chapter 33.2.3.5.7.1, Sprinklers in attics, or Chapter 33.2.3.5.7.2, Heat detection systems in attics of the Life Safety Code. 5

Automatic Sprinkler Requirement & Attic Used Section 33.2.3.5.7.1 of the NFPA 101: ICFs-IID where an automatic sprinkler system is installed, as required by LSC, and the attic is used for living purposes, storage, or fuelfired equipment: – Attic, shall be protected with automatic sprinklers that are part of the required, approved automatic sprinkler system in accordance with 9.7.1.1 of the LSC. 6

Automatic Sprinkler Requirement & Attic Not Used Section 33.2.3.5.7.2 of the NFPA 101: ICFs/IID where an automatic sprinkler system is installed, as required by the LSC, and the attic is not used for living purposes, storage, or fuel-fired equipment: – Attic, shall meet one of the following criteria: 7

Attic Criteria Attics shall be protected with automatic sprinklers that are part of the required, approved automatic sprinkler system in accordance with 9.7.1.1 of the LSC. or Attics shall be protected throughout by a heat detection system arranged to activate the building fire alarm system in accordance with Section 9.6 of the LSC. or 8

Attic Criteria Attics shall be of noncombustible or limited-combustible construction. or Attics shall be constructed of fireretardant-treated wood in accordance with NFPA 703, Standard for Fire Retardant-Treated Wood and Fire-Retardant Wood and FireRetardant Coatings for Building Materials. 9

Automatic Sprinkler Not Required Where an automatic sprinkler system is not required by the LSC, ICF-IID are not subject to these specific attic protection requirements. 10

Compliance If an ICF-IID is required by the LSC to have a sprinkler system and attic fire protection requirements are not met, immediately: – Assess attic space for use and contents – Determine attic construction materials – Take steps needed to achieve compliance State Survey Agencies will survey to determine compliance with this requirement starting July 5, 2019. 11

Life Safety Code Waiver ICFs-IID are permitted to meet either the Residential Board and Care Occupancies chapter or the Health Care Occupancy chapters of the LSC. For ICFs-IID that meet the Health Care Occupancy chapters of the LSC: – If the requirement for the attic fire protection would result in unreasonable hardship for the ICFIID, then CMS may waive specific provisions of the LSC, but only if the waiver does not adversely affect the health and safety of clients. 12

Summary In conclusion, this presentation reviewed the following: 1. Regulatory requirements for the attic fire safety requirement 2. Attic protection requirements for occupied or used attic spaces 3. Attic protection requirements for unoccupied or unused attic spaces 4. Health care occupancy waiver 13

Questions Questions related to the life safety code requirements for ICF/IID can be submitted to the following mailboxes: QSOG [email protected] & QSOG [email protected] 14